Metrel CS 2099 Installation Tester Field Verification CheckboxOverview The Metrel CS 2099 Installation Tester Field Verification Checkbox is a multifunction device designed to allow periodic checks of installation testers for basic accuracy and functionality. Ideal for weekly or monthly checks in between formal 3rd party traceable calibrations, it provides a quick and easy way to verify essential functions. The device provides the capability to verify: Insulation calibration up to 1000V Continuity function
Overview
The Metrel CS 2099 Installation Tester Field Verification Checkbox is a multifunction device designed to allow periodic checks of installation testers for basic accuracy and functionality. Ideal for weekly or monthly checks in between formal 3rd party traceable calibrations, it provides a quick and easy way to verify essential functions.
The device provides the capability to verify:
- Insulation calibration up to 1000V
- Continuity function calibration
- Fault loop impedance calibration with RCD trip-lock function
- Calibration of RCD trip-out time measurement
- Line impedance calibration
- Voltage and frequency calibration
- Measurement of leads verification
- PE test terminal functional verification
- Automatic mains polarity verification
Specifications
Insulation Resistance
- 2.0 MOhm - Accuracy +-1%
- 50 MOhm - Accuracy +-1%
- Maximum test voltage: 1500V DC (1200V DC continuously)
Low Resistance
- 0.5 Ohm - Accuracy +-2%
- 5.0 Ohm - Accuracy +-2%
- 15 Ohm - Accuracy +-2%
- Maximum test current: 220mA DC
Voltage and Frequency
- 50.0V @ 230V AC
- Short-circuit current: <6mA
- Nominal output resistance: 25 kOhm
Fault Loop Impedance, Trip-Lock Impedance, Line Impedance
- 1.2 Ohm (Existing circuit loop impedance + 0.2Ohm) - Accuracy +-0.2Ohm
- 11 Ohm (Existing circuit loop impedance + 11Ohm) - Accuracy +-0.5Ohm
RCD Trip-Out Time Simulation and Current Measurement
- Current reference value 30mA - Accuracy +-1%
- Trip-out time reference value 30mA - Accuracy +-2ms
- Current Low Indication 28mA - Accuracy +-1mA
- Current High Indication 35mA - Accuracy +-1mA
Standard Warranty
The product comes with a 1-year standard warranty.
Shipping Notes
- Free Standard Shipping on $100+ Orders to the USA.
- Except Preorder products are shipped in 48 hours.
- Delivery to the USA:
- Standard Shipping : 3-10 business days
- If time is of the essence, please consider selecting expedited delivery for faster service.
Exchange/Return Notes
- We offer a 30-day return/exchange service after receiving.
- Final sale items are not eligible for returns or exchanges.
- To process your return/exchange, please contact us at [email protected]
- Please click here for more details>>> Return & Exchange Policy